Application:
The instrument is used for process control and conductivity measure and control in single stage reverse osmosis producing water system, manage to simplify the complicated industrial process
Features:
The Dot matrix LCD128×64 screen, Chinese / English menu display
With Typical reverse osmosis system operation program inside, users only need to set the parameters
Automatic range, digital temperature compensation, calculation of desalination
Each checking terminal adopt low voltage, photoelectricity seclusion input
All control terminal adopt dry contact
Isolated 485 connection, standard Modbus communication agreement (RTU)
Calibration of electrode constant, setting of conductivity limit alarm
DC24V power supply meets operation in damp working place.
Model: CCT-8320
Auxiliary electrode constant: 1.0cm-1
Power supply: DC 24V
Reverse osmosis control point:
raw water tank high level, raw water tank low level,
low pressure alarm, high p ressure alarm, pure water
tank high level, pure water low level, pretreatment
reverse flush chain
Reverse osmosis collection point:
inlet valve, low pressure pump, high pressure pump,
flush valve,conductivity over-limit discharge valve
Display mode: backlight LCD128×64 dot matrix, chinese / english menu
Accuracy: ≤ 1.5%(FS)
Temperature compensation:
calculate temperature compensation with 25℃ as the reference temperature
Working environment: temperature: 0-50℃ humidity : ≤85%RH
Control output mode: ON single contact relay dry contact output
Contactor capacity: AC 230V/5A(Max);AC 115V/10A(Max)
Alarm mode: Buzzer on/off
Protection level: IP65(with rear cover)
Outline dimension: 96mm×96mm×105mm(H×W×D)
Hole size: 91mm×91mm(H×W)
Fix mode: panel mounted
|
??????? ???????? ?????? ?????